NOTE:
1. For the dual control type, the manual control mode is not available.
2. Though the display of manual output can be set in 0.1% unit, the
actual output resolution is 1%.
3. Autotuning cannot be executed in the manual mode.
4. Power supply is off during manual operation, the value of
becomes 0.0%.
5. When the manipulated variable is changed during manual operation,
the proportion cycle being output at that changing point is followed
by the next proportion cycle which starts the actual output of
changed MV.
ogy Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE |
Present cycle
Output changed from
50%~20%
Next cycle
20% output started
70