Changing scale
(voltage/current input)
If it is used for voltage or current input, input scaling is possible.
Input scaling
Engineering dimensions can be set to voltage or current input.
Setting procedure
NOTES: When setting the scale, set it so that the difference between
ogy Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE |
(maximum value on scale):
(minimum value on scale):
(decimal-point location):
and
following condition must always be satisfied when setting is
made:
is larger than
Parameter to be used
Engineering value
equivalent to the 100% input is set
(-1999 ~ 9999).
Engineering value
equivalent to the 0% input is set (-
1999 ~ 9999).
Decimal point location is
set (see below). (0 ~ 2)
(No decimal point)
0
1
2
(span) does not exceed 9999. The
.
41

Advertisement