gefran GFX4-IR Configuration And Programming Manual page 19

4-zone modular power controller for ir lamps and inductive loads
Table of Contents

Advertisement

ADVANCED SETTINGS
Input filter
412
FT. T U
Sets a low pass filter on the auxiliary TV input, running the average of values read in the
specified time interval. If = 0 , excludes the average filter on sampled values.
FUNCTIONAL DIAGRAM
Single-phase load
Voltmeter
input
phase1
FUNCTIONAL DIAGRAM
3-phase load
Voltmeter
input
phase1
Voltmeter
input
phase2
Voltmeter
input
phase3
80415F_MSW_GFX4-IR_05-2019_ENG
Digital filter for auxiliary TV input (phase
R/W
1, 2 and 3)
Scale limits,
Offset
(o.tV1)
Variable I.tV1
Scale limits,
Offset
(o.tV1)
Variable I.tV1
Scale limits,
Offset
(o.tV2)
Variable I.tV2
Scale limits,
Offset
(o.tV3)
Variable I.tV3
0.0 ... 20.0 sec.
Filter
Variable I.VF1
low pass
(Ft.tV)
Filter
Variable I.VF1
low pass
(Ft.tV)
Filter
Variable I.VF 2
low pass
(Ft.tV)
Filter
Variable I.VF 3
low pass
(Ft.tV)
Phase
voltage
see generic
alarms
I.V21
Line
I.V32
voltage
I.V13
2.0
19