gefran GFX4-IR Configuration And Programming Manual page 22

4-zone modular power controller for ir lamps and inductive loads
Table of Contents

Advertisement

Read state
602
In. 2
606
Er. 2
ADVANCED SETTINGS
Input filter
604
FLt. 2
Sets a low pass filter on the auxiliary input, running the average of values read in the
specified time interval. If = 0 , excludes the average filter on sampled values.
FUNCTIONAL DIAGRAM
Auxiliary
input
22
R
Value of auxiliary input
Error code for self-diagnosis
R
of auxiliary input
R/W
Digital filter for auxiliary input
Select sensor
(AI.2)
0
No error
1
Lo (value of process variable is < Lo.S)
2
Hi (value of process variable is > Hi.S)
3
ERR [third wire interrupted for PT100 or input values below minimum
limits (ex.: for TC with connection error)]
4
SBR (probe interrupted or input values beyond maximum limits)
0.0 ... 20.0 sec
Scale limits, decimal
point, Offset (H.S2,
L.S2, dP.2, oFS.2)
Error code table
Low pass f
Internal In.2
ilter
(Flt.2)
80415F_MSW_GFX4-IR_05-2019_ENG
0.1
See generic
alarms and
Control