2.1.3.5 Technical Data

Module Specific Data
Number of inputs
Voltage supply
Current consumption
Sensor types
Sensor connection
Temperature range
Resolution
Conversion time
Response delay
(time from starting or connecting the sensor to
the first proper measured value)
Measuring error
(The specified accurancys apply to a supply line
resistance of R
Temperature coefficient
Isolation
Measured current
Bit width
Dimensions (mm) W x H x L
Weight
Standards and Regulations (cf. Chapter 2.2 of the Coupler/Controller Manual)
EMC-Immunity to interference (CE)
EMC-Emission of interference (CE)
Approvals (cf. Chapter 2.2 of the Coupler/Controller Manual)
More Information
Detailed references to the approvals are listed in the document "Overview
Approvals WAGO-I/O-SYSTEM 750", which You can find on the CD ROM
ELECTRONICC Tools and Docs (Item-No.: 0888-0412-0001-0101) or in the
Internet under:
www.wago.com
/WAGO-I/O-SYSTEM 750/System Description/.
WAGO-I/O-SYSTEM 750
I/O Modules
(internal)
max.
max.
< 1 Ohm)
L
typ.
UL
(UL508)
C
US
Conformity Marking
-> Service /Downloads /Documentation
750-461/020-000 [2 AI NTC 20kOhm] • 25
2
via system voltage DC /DC
65 mA
NTC 20kOhm
2-wire
-30 °C ... +130 °C
0,1 °C
320 ms (per channel)
4 s
<± 1,0 K in the range of –30 °C ... +50 °C
(<± 0,5 K at 25 °C)
<± 2,0 K in the range of +50 °C ... +100 °C
<± 3,0 K in the range of +100 °C ... +130 °C
<± 0,002 % /K of full scale value
400 V (system/supply)
0,05 mA at 25 °C
2 x 16 bits data
2 x 8 bits Control/Status (option)
12 x 64* x 100
* from upper edge of 35 DIN rail
ca. 55 g
acc. to EN 61000-6-2 (01)
acc. to EN 61000-6-3 (01)