AKD2G/AKD/S700 Accessories Manual | 13.7.4 Motor Power Cable Specifications
13.7.4 Motor Power Cable Specifications
All cables supplied with AKD and S700 drives are RoHS compliant.
13.7.4.1 Cable Routing Standards
UL 508C and UL 508A indicate that wires, when routed together, shall be rated for the highest voltage
involved in all of the circuits. This means that value line feedback cables which are 300V rated are not
appropriate when routed directly next to motor power cables that carry more voltage than 300V. They
should be physically seperated. Performance line cables are recommended when this is a concern.
The NFPA 70 (NEC) article 300.3(C)(1) says that for circuits that are 600V or less, conductors of ac
and dc circuits shall be permitted to occupy the same equipment wiring enclosure, cable, or raceway.
All conductors shall have an insulation rating equal to at least the maximum circuit voltage applied to
any conductor within the enclosure, cable, or raceway.
13.7.4.2 AKD 1.5 – 6 A Power Cable, VP-507BEAN-xx
Cable Specifications
Cable jacket material
Outside diameter
Bend radius
Static flex rating
Dynamic flex rating
Temperature rating
Voltage rating
RoHS Compliant
Assembly Weight:
VP-507BEAN-01
VP-507BEAN-03
VP-507BEAN-06
VP-507BEAN-09
VP-507BEAN-12
66 Kollmorgen™ | kdn.kollmorgen.com | November 2019
TPE
9.4 mm ± 0.25 mm
94 mm
Not rated
Not rated
105 C
Cable Routing Standards
600 V (see
Yes
0.258 kg
0.536 kg
0.955 kg
1.372 kg
1.789 kg
)