Time Table And Settings For Program Sequence Pme71.402 - Siemens LME7 Series Basic Documentation

Burner control
Hide thumbs Also See for LME7 Series:
Table of Contents

Advertisement

11.3 Time table and settings for program sequence PME71.402...

Type
TSA
PME71.402...
tw
max.
Requirements
2.5
3
Factory setting
---
t3n+0.45
Max.
2.5
14
Min.
---
---
Step size
---
---
Function parameter
Continuous pilot
0: OFF
1: ON
Repetition in the event of loss of flame during operation
<2: None
= 2: 1 x
Legend
tw
Waiting time
TSA
Safety time
t1
Prepurge time
t3
Preignition time
t3n
Postignition time (P257 +0.3 seconds)
1)
Response time to a change of signal by the air pressure switch (opens) and response time in the event of loss of flame
2)
Response time to a change of signal by the inputs (e.g. pressure switch-min)
3)
Flame detection time
Building Technologies Division
Infrastructure & Cities Sector
Times in seconds
t1
t3
t3n
P225
P226
P257
min.
min.
approx.
30
3
2.5
29.106+2.1
3.087
2.205+0.3
3.234
1237+2.1
37.485
13.23+0.3
74.97
0+2.1
1.029
0+0.3
3.234
4.851
0.147
0.147
0.294
Parameter number
Basic Documentation LME7...
11 PME71.402...
t4
t8
t9
t10
P230
P234
P231
P224
min.
min.
approx.
approx.
3
15
3
15
19.404
2.646
13.818
1237
74.97
13.818
0
0
0
4.851
0.294
0.294
Factory setting
P247
0
P240
0
t4
Interval: End of safety time – fuel valve 1 ON
t8
Postpurge time
t9
Interval: Fuel valve 1 ON and pilot valve OFF
t10
Specified time air pressure switch state message (timeout)
nd
t22
2
safety time
t22
1)
2)
3)
approx.
---
---
---
---
t9+1
---
---
---
---
1
0.45
0.45
---
0.3
0.3
---
---
---
---
---
58/245
CC1P7105en
29.11.2011

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents