Measuring circuit for detector
current measurement
Building Technologies Division
Infrastructure & Cities Sector
Ionization probe
M
LME7...
X10-05/2
C
X10-05/1
Figure 4: Measuring circuit for ionization probe
Legend
C
Electrolytic condenser 100...470 µF; DC 10...25 V
ION
Ionization probe
Microammeter Ri max. 5,000 
M
Warning!
Simultaneous operation of QRA... and ionization probe is not permitted!
If not observed, there is a risk of impairment of safety functions.
Basic Documentation LME7...
4 Technical data
ION