Installation notes
Building Technologies Division
Infrastructure & Cities Sector
1.2

Mounting notes

 Ensure that the relevant national safety regulations are complied with
 In the geographical areas where DIN regulations are in use, the requirements of
VDE must be satisfied, especially DIN/VDE 0100, 0550 and DIN/VDE 0722
 The LME7... basic unit must be secured with fixing screws M4 (UNC32) or M5
(UNC24), observing a maximum tightening torque of 1.8 Nm and using all 3 fixing
points. The additional mounting surfaces on the housing are provided to improve
mechanical stability. These must fully rest on the mounting surface to which the unit
is secured. The flatness of that mounting surface must be within a tolerance band of
0.3 mm
13
Operating panel
7113z05e/0810
Figure 1: Mounting – mounting surface