<3 s
It will now be displayed for 2 minutes, or can be finished by pressing the
<2
min
or
/reset
Note:
During backup, all settings and parameters are transferred from the basic unit's memory to the
memory of the program module.
Warning!
If any parameters are changed, a backup must be made! If this is not observed, there is a
risk of loss of safety functions.
Building Technologies Division
Infrastructure & Cities Sector
Basic Documentation LME7...
23 Operation via AZL2...
Press
for value 1.
Display: Value 1 blinks
/reset
Press
to activate the backup process.
/reset
Display shows run
After approx. 3 seconds (depending on the duration of the
program sequence), the displays shows bAC End and
signals the end of the backup process.
Display: bAC End
Display shows OFF when the backup process is finished.
button
/reset
189/245