Reading The Value Of Parameter 920 In The Prepurge Phase (P30) And Ignition Load Phase (P38, P40 And P44); Procedure - Siemens LME7 Series Basic Documentation

Burner control
Hide thumbs Also See for LME7 Series:
Table of Contents

Advertisement

Procedure

Building Technologies Division
Infrastructure & Cities Sector
permissible ignition speed close to the overvoltage limit. If this is not observed, there
is a risk of loss of safety functions.
27.4.2 Reading the value of parameter 920 in the prepurge
phase (P30) and ignition load phase (P38, P40 and P44)
Set the ignition load speed (P0) for the burner to the maximum permissible value,
and the prepurge speed (503.01) to the minimum value
Let the AZL2... display service mode. Press
shows InFo, then SEr
Release
so that parameter number 701.00 starts blinking
/reset
Press
or
to select parameter 920 (blinking)
Start the burner
Read the value of parameter 920 in the prepurge phase (P30) and ignition phase
(P38, 40 and 44). Write down the values. They will be required as a basis for
setting safety parameter 675.00
ESC
By pressing
setting level and return to the initial mode
Note:
If the onboard operating panel of the LME7... basic unit changes from phase display
(e.g. P30) to SEC at 1-second intervals, or if the LME7... goes to lockout (Loc: 225),
the difference between the actually required PWM value (parameter 936) and safety
parameter 675.00 or 675.01 is too small. Decrease value 675.00 (parameter 920 -
1%) or increase value 675.01 (parameter 920 +1%). Reduce the value until SEC
disappears from the display.
Basic Documentation LME7...
27 PWM settings
/reset
(press
and
simultaneously) you leave the parameter
for >3 seconds. The display first
CC1P7105en
228/245
29.11.2011