Mounting notes

Installation notes

Building Technologies Division
Ensure that the relevant national safety regulations and notes on standards are
complied with
In geographical areas where DIN regulations apply, the mounting and installation
requirements of VDE must be satisfied, especially DIN/VDE 0100, 0550 and
DIN/VDE 0722
Make certain that the actuator is not exposed to direct solar radiation
Required tightening torques for the fixing screws of the
- housing cover: 3.5 Nm
- connecting cover: 2 Nm
Note!
Ensure correct direction of rotation!
SQM40... (left, CCW)
90°
Ensure that the electrical wiring is in compliance with national and local safety
regulation
Make certain that strain relief of the connected cables conforms to the relevant
standards (e.g. as per DIN EN 60730 and DIN EN 60335)
Ensure that spliced wires cannot get into contact with neighboring terminals. Use
adequate ferrules
Unused terminals of the SQM40.../SQM41... must be covered by dummy plugs
When making the wiring, the AC 120 V or AC 230 V section must be separated from
other voltage sections, thus ensuring protection against electric shock hazard
The connection between the actuator drive shaft and the relevant controlling element
must be form-fitted
Only plastic versions of cable glands may be used
SQM41... (right, CW)
90°
CC1N7817en
3/26
24.02.2015