Mounting instructions
Mounting position
Device protection
Mounting bracket
Factory setting
Manual adjustment
Mechanical limitation of
angular rotation
Damper shafts
Use of rotary/linear sets
Tandem (powerpack)
mounting
Siemens
Smart Infrastructure
5

Mounting notes

All information and steps to properly prepare and mount the actuator are available in
the mounting instructions 4 319 2685 0 (M4626) delivered with the actuator. The shaft
adapter as well as all other individual parts are not premounted, as the actuator
components are put together differently depending on damper shaft length. Refer to
section 2.5 "Mechanical design".
Choose the actuator's mounting position so that you can easily access the cables as
well as the setting elements on the front of the actuator. Refer to section
11.1 "Dimensions".
To satisfy the IP54 protection class requirements, the following conditions must be
fulfilled:
·
The actuators are equipped only for vertical mounting (cable entries at bottom) with
air dampers having a horizontal shaft.
·
The actuator mounted on the damper shaft may be mounted by max. +/– 45° to the
vertical line:
·
Use the weather shield ASK75.1 for any mounting position.
The mounting bracket (see dimensions) is required for mounting on the damper shaft.
The insertion depth for the bolt into the housing must be sufficient and guaranteed.
The actuator comes with a factory setting of +2.5° which ensures a tight close-off for
the air dampers.
The actuator can be manually adjusted by pressing the g ear train disengagement
button .
To ensure a tight close-off function for the dampers and the exact switching position for
switches A and B, adjust the actuator only if the shaft adapter and the position
indicator are mounted in accordance with the mounting instructions.
If necessary, you can limit the angular rotation at increments of 5° for the entire span by
positioning the shaft adapter in the respective position.
Refer to chapter 8 Technical data for information on minimum length and diameter of
the damper shafts.
Mount the mounting sets for converting a rotary movement to linear movement (section
2.2 Type summary) as per the separate mounting instructions.
When mounting two actuators on the same damper shaft (for GBBGIB13..1 and
GBB/GIB33..1), use the ASK73.1 mounting bracket.
For GBB/GIB16.. use the ASK73.2 mounting bracket.
Rotary actuators without spring return GBB/GIB..1