Connect the stripped cables (see Figure 17 and Table 10) as shown in
Figure 24.
Expose the shield of all three cables in order to make a 360-degree con-
nection with the cable clamp (1).
Connect the (phase) conductors of the supply, brake and motor cables
7
into their respective terminals (2).
Form the rest of the cable shield of all three cables into "pigtails" and make
a grounding connection with a clamp as shown in Figure 24 (3).
Make the pigtails just long enough to reach and be fixed to the terminal -
not longer.
3
Tightening torques of cable terminals:
Frame
Type
MR4 C 0015—C 0075 0.5—0.6 4.5—5.3
MR5 C 0100—C 0200 1.2—1.5 10.6—13.3 1.5
MR6 C 0250—C 0400 10
MR7 C 0500—C 0750 8/15
*. Cable clamping (Ouneva Pressure Terminal Connector)
2
1
Figure 24.
Tightening torque
[Nm]/[lb-in.]
Power and motor
terminals
[Nm]
lb-in.
88.5
*
70.8/132.8* 1.5
Table 11. Tightening torques of terminals
Tightening torque
[Nm]/[lb-in.]
EMC grounding
clamps
[Nm]
lb-in.
1.5
13.3
13.3
1.5
13.3
13.3
P
OWER CABLING
3
Tightening torque,
[Nm]/[lb-in.]
Grounding terminals
[Nm]
lb-in.
2.0
17.7
2.0
17.7
2.0
17.7
8/15*
70.8/132.8*