The drive produces heat in operation and is cooled by air circulated by a fan. Enough free
space needs to be left around the drive to ensure sufficient air circulation and cooling. Different
acts of maintenance also require a certain amount of free space.
Make sure that the temperature of the cooling air does not exceed the maximum ambient tem-
perature of the converter.
C
A
A
D
Figure 14. Installation space
A = clearance around the drive (see also B)
B = distance from one drive to another or distance to cabinet wall
C = free space above the drive
D = free space underneath the drive
B
B
NK5_ 2
Min clearance [in], NEMA1
*
Type
A
MR4
.79
MR5
.79
MR6
.79
MR7
.79
MR8
.79
MR9
.79
*. Min clearances A and B for
drives with IP54 enclosure is 0
in.
Table 5. Min. clearances around drive
Honeywell
• 18
B
C
D
*
.79
3.94 1.97
.79
4.72 2.36
.79
6.30 3.15
.79
9.84 3.94
.79
11.8 5.91
.79 13.78 7.87