Honeywell SmartVFD HVAC MR4 User Manual page 132

Variable frequency drives for constant and variable torque applications
Table of Contents

Advertisement

HVAC A
PPLICATION
3.5.15
Group 3.13: PID-controller 2
3.5.15.1
Basic settings
For more detailed information, see chapter 3.5.14.
Code
Parameter
M3.13.1.1
Enable PID
M3.13.1.2
Output in Stop
M3.13.1.3
PID gain
M3.13.1.4
PID integration time
M3.13.1.5
PID derivation time
M3.13.1.6
Process unit selection
M3.13.1.7
Process unit min
M3.13.1.8
Process unit max
M3.13.1.9
Process unit decimals
M3.13.1.10
Error inversion
M3.13.1.11 Dead band hysteresis
M3.13.1.12
Dead band delay
3.5.15.2
Setpoints
Code
Parameter
M3.13.2.1
Keypad setpoint 1
M3.13.2.2
Keypad setpoint 2
M3.13.2.3
Setpoint ramp time
Setpoint source 1
M3.13.2.4
selection
M3.13.2.5
Setpoint 1 minimum
M3.13.2.6
Setpoint 1 maximum
Setpoint source 2
M3.13.2.7
selection
M3.13.2.8
Setpoint 2 minimum
M3.13.2.9
Setpoint 2 maximum
Min
Max
Unit
0
1
0.0
100.0
%
0.00
1000.00
%
0.00
600.00
s
0.00
100.00
s
0
40
Varies
Varies
Varies
Varies
Varies
Varies
0
4
0
1
Varies
Varies
Varies
0.00
320.00
s
Table 46.
Min
Max
Unit
0.00
100.00
Varies
0.00
100.00
Varies
0.00
300.00
s
0
16
-200.00
200.00
%
-200.00
200.00
%
0
16
-200.00
200.00
%
-200.00
200.00
%
Table 47.
Default
ID
0 = Disabled
0
1630
1 = Enabled
The output value of the PID
controller in % of its maxi-
0.0
1100
mum output value while it is
stopped from digital input
100.00
1631
1.00
1632
0.00
1633
1
1635
0
1664
100
1665
2
1666
0
1636
0.0
1637
0.00
1638
Default
ID
0.00
1640
0.00
1641
0.00
1642
1
1643
Minimum value at analog
0.00
1644
signal minimum.
Maximum value at analog
100.00
1645
signal maximum.
0
1646 See M3.13.2.4.
Minimum value at analog
0.00
1647
signal minimum.
Maximum value at analog
100.00
1648
signal maximum.
Honeywell
• 60