Honeywell SmartVFD HVAC MR4 User Manual page 120

Variable frequency drives for constant and variable torque applications
Table of Contents

Advertisement

HVAC A
PPLICATION
3.5.9
Group 3.7: Prohibit Frequencies
In some systems it may be necessary to avoid certain frequencies due to mechanical reso-
nance problems. By setting up prohibit frequencies it is possible to skip these ranges.
Code
Parameter
Prohibit frequency
M3.7.1
range 1 low limit
Prohibit frequency
M3.7.2
range 1 high limit
Prohibit frequency
M3.7.3
range 2 low limit
Prohibit frequency
M3.7.4
range 2 high limit
Prohibit frequency
M3.7.5
range 3 low limit
Prohibit frequency
M3.7.6
range 3 high limit
M3.7.7
Ramp time factor
Resonance sweep
M3.7.8
acc/dec time
Min
Max
Unit
-1,00
320,00
Hz
0,00
320,00
Hz
0,00
320,00
Hz
0,00
320,00
Hz
0,00
320,00
Hz
0,00
320,00
Hz
0,1
10,0
Times
0.1
3000.0
s
Table 34. Prohibit frequencies
Default
ID
0,00
509
0 = Not used
0,00
510
0 = Not used
0,00
511
0 = Not used
0,00
512
0 = Not used
0,00
513
0 = Not used
0,00
514
0 = Not used
Multiplier of the currently
1,0
518
selected ramp time between
prohibit frequency limits.
Acceleration and decelera-
20.0
1812
tion times to be used during
resonance sweep.
Honeywell