Honeywell SmartVFD HVAC MR4 User Manual page 162

Variable frequency drives for constant and variable torque applications
Table of Contents

Advertisement

HVAC A
PPLICATION
Fault
ID
Fault name
code
Fieldbus com-
munication
53
1053
fault
Slot A fault
1354
Slot B fault
1454
54
1654
Slot D fault
1754
Slot E fault
PC communi-
65
1065
cation fault
Thermistor
66
1066
fault
Maintenance
counter 1
1301
alarm
Maintenance
1302
counter 1 fault
Maintenance
counter 2
1303
alarm
68
Maintenance
1304
counter 2 fault
Maintenance
counter 3
1305
alarm
Maintenance
1306
counter 3 fault
1310
Fieldbus map-
69
1311
ping error
1312
Process super-
vision fault
101
1101
(PID1)
Process super-
vision fault
105
1105
(PID2)
Possible cause
The data connection between the field-
bus master and fieldbus board is broken
Defective option board or slot
The data connection between the PC
and drive is broken
The thermistor input has detected an
increase of motor temperature
Maintenance counter has reached the
alarm limit.
Maintenance counter has reached the
fault limit.
Maintenance counter has reached the
alarm limit.
Maintenance counter has reached the
fault limit.
Maintenance counter has reached the
alarm limit.
Maintenance counter has reached the
fault limit.
Non-existing ID number is used for map-
ping values to Fieldbus Process Data
Out.
Not possible to convert one or more val-
ues for Fieldbus Process Data Out.
Overflow when mapping and converting
values for Fieldbus Process Data Out
(16-bit).
PID controller: Feedback value outside
of supervision limits (and the delay if
set).
PID controller: Feedback value outside
of supervision limits (and the delay if
set).
Table 55. Fault codes and descriptions
Honeywell
• 90
Remedy
Check installation and field-
bus master.
Check board and slot
Check motor cooling and
load.
Check thermistor connection
(If thermistor input is not in
use it has to be short cir-
cuited)
Carry out the needed mainte-
nance and reset counter.
Check parameters in Field-
bus Data Mapping menu
(chapter 3.5.8).
The value being mapped may
be of undefined type. Check
parameters in Fieldbus Data-
Mapping menu (chapter
3.5.8).