PPLICATION
3.5.3.2
Motor Control Settings
Code
Parameter
M3.1.2.1
Switching frequency
M3.1.2.3 Motor preheat function
Motor preheat temper-
M3.1.2.4
ature limit
M3.1.2.5
Motor preheat current
Min
Max
Unit
1.5
Varies
0
3
-20
80
0.5*I L
0
Table 23. Advanced motor settings
Default
ID
kHz
Varies
601
0
1225
°C
0
1226
A
Varies
1227
Honeywell
• 34
Description
Motor noise can be mini-
mised using a high switch-
ing frequency. Increasing
the switching frequency
reduces the capacity of the
drive. It is recommended to
use a lower frequency when
the motor cable is long in
order to minimize capaci-
tive currents in the cable.
0 = Not used
1 = Always in stop state
2 = Controlled by DI
3 = Temperature limit (heat-
sink)
NOTE:
Virtual digital input
can be activated by RTC
Motor preheat is switched
on when the heatsink tem-
perature goes below this
level (if par. M3.1.2.3 is set
Temperature limit
to
.
If limit is e.g. 10°C feeding
current starts at 10 °C and
stops at 11°C (1-degree
hysteresis).
DC current for pre-heating
of motor and drive in stop
state. Activated by digital
input or by temperature
limit.