Honeywell SmartVFD HVAC MR4 User Manual page 122

Variable frequency drives for constant and variable torque applications
Table of Contents

Advertisement

HVAC A
PPLICATION
3.5.11
Group 3.9: Protections
Code
Parameter
Response to Analog
M3.9.1
input low fault
Response to external
M3.9.2
fault
Response to Input
M3.9.3
phase fault
M3.9.4
Undervoltage fault
Response to output
M3.9.5
phase fault
Motor thermal protec-
M3.9.6
tion
Motor ambient temper-
M3.9.7
ature factor
Motor thermal zero
M3.9.8
speed cooling
Motor thermal time
M3.9.9
constant
Motor thermal loadabil-
M3.9.10
ity factor
M3.9.11
Motor stall fault
Underload fault (bro-
M3.9.12
ken belt/dry pump)
Response to Fieldbus
M3.9.13
communication fault
Slot communication
M3.9.14
fault
M3.9.15
Thermistor fault
M3.9.16
Soft fill timeout
Response to PID1
M3.9.17
supervision fault
Response to PID2
M3.9.18
supervision fault
Min
Max
Unit
0
4
0
3
0
3
0
1
0
3
0
3
-20.0
100.0
°C
5.0
150.0
%
1
200
min
0
150
%
0
3
0
3
0
4
0
3
0
3
0
3
0
3
0
3
Table 36. Protections settings
Default
ID
0=No action
1=Alarm
2=Alarm, set preset fault fre-
0
700
quency (par. M3.3.19)
3=Fault (Stop according to
stop mode)
4=Fault (Stop by coasting)
0 = No action
1 = Alarm
2
701
2 = Fault (Stop according to
stop mode)
3 = Fault (Stop by coasting)
3
730
See above
0 = Fault stored in history
0
727
1 = Fault not stored in history
2
702
See M3.9.2
2
704
See M3.9.2
40.0
705
Ambient temperature in °C
Defines the cooling factor at
zero speed in relation to the
Varies
706
point where the motor is run-
ning at nominal speed with-
out external cooling.
The time constant is the time
within which the calculated
Varies
707
thermal stage has reached
63% of its final value.
100
708
0
709
See M3.9.2
0
713
See M3.9.2
3
733
See M3.9.1
2
734
See M3.9.2
0
732
See M3.9.2
2
748
See M3.9.2
2
749
See M3.9.2
2
757
See M3.9.2
Honeywell
• 50
Description

Hide quick links: