2.9
Maximum configuration and configuration options with power
modules
Maximum configuration
Every ET 200X consists of a basic module and up to seven expansion modules, of
which a maximum of seven expansion modules can be
PM 148 DO 4
Restrictions imposed by power input
The maximum system configuration is limited amongst other things by the power
input of the load of the digital output modules in the configuration (see Section 2.7).
Limits for current consumption by load without use of power modules:
Limits for one ET 200X
Raising the limit
If the power input from the load exceeds the above limits, use power modules that
correspond to the load power consumption of your configuration. A power module
provides 10 A of load current for the downline digital-output modules.
2-16
DC 24V/2A power modules.
Up to 40 _C: v 10 A
Up to 55 _C: v 8 A
Limits for ET 200X overall configuration
(load voltage looped through)
Up to 40 _C: v 16 A
Up to 55 _C: v 12 A