Parameters Of The Analog Inputs And Outputs - Siemens SIMATIC ET 200X Manual

Distributed i/o device
Table of Contents

Advertisement

7.21.1

Parameters of the analog inputs and outputs

Parameter assignment
You set the parameters of the analog inputs/outputs using either the STEP 7 or
COM PROFIBUS parameter assignment software.
Parameters
The tables below give an overview of the of the parameters that you can set for the
analog inputs and analog outputs.
You can find the layout of the parameter assignment frame and the assignment of
the bits including the parameters of the analog inputs and outputs in the
configuration and parameter assignment frame of the ET 200X at
http://www.ad.siemens.de/simatic-cs. In Section 5.4 you will find the
parameterizable diagnostics and in Section 5.5 you will find an in-depth description
of diagnostic and hardware interrupt handling.
Table 7-41 Parameters of analog inputs
Expansion modules with
All
All
All
EM 144 AI 2
I
(6ES7 144-1GB31-0XB0 and
6ES7 144-1GB41-0XB0)
EM 144 AI 2
RTD
(6ES7 144-1JB31-0XB0)
EM 144 AI 2
I
(6ES7 144-1GB31-0XB0)
EM 145 AO 2
I
(6ES7 145-1GB31-0XB0)
All
ET 200X Distributed I/O Device
EWA 4NEB 780601602-06
Parameters
Range
Format
SIMATIC S7
format/
SIMATIC S5
format
Enable
S
Diagnostic
Yes/no
interrupt
S
Hardware
Yes/no
interrupt
upon limit
value
violation
Diagnosis
S
Group
Yes/no
diagnosis
Diagnosis
S
With wire
Yes/no
break
check
Measuring
20 mA/4 to
range
20 mA
Measuring
20 mA/4 to
range
20 mA
1
Reset time
16.7 ms/20 ms
Technical Specifications
Default
Area affected
SIMATIC S7
Expansion Module
format
Expansion module
No
No
Channel
No
Channel
No
4 to 20 mA
Channel
4 to 20 mA
Channel
20 ms
Channel (module
channels must be
identically set)
7-85