Technical data
Dimensions and weight
Dimensions
W
H
D (mm)
Weight
Module-specific data
Number of inputs
Cable length
S
Unshielded
Voltages, currents, potentials
Maximum number of in-
puts driven simulta-
neously
S
All installed positions
max. 55 _C
Electrical isolation
Permissible potential diffe-
rence
S
Between different
circuits
Insulation tested with
Power input
S
From backplane bus
(1L+)
Power loss of module
Status, alarms, diagnostics
Status display
Alarms
S
Hardware interrupt
S
Diagnostic interrupt
Diagnostic functions
S
Group error
S
Channel error display
S
Reading diagnostic
information
ET 200X Distributed I/O Device
EWA 4NEB 780601602-06
87
110
55
Approx. 250 g
8
Max. 30 m
8
No
75 VDC, 60 VAC
500 VDC
Max. 30 mA
Typ. 1.5 W
Green LED per chan-
nel
Hardware interrupt
Diagnostic interrupt
*
Configurable
** The required closed-circuit current for wire break
Configurable
Configurable
Red LED (SF)
Red LED per channel
Possible
Technical Specifications
Sensor supply outputs
Outputs
Output current*
Aggregate current
Short-circuit protection
Sensor selection data
Input voltage
S
Rated value
S
With signal "1"
S
With signal "0"
Input current
S
With signal "1"
Input delay (parameteriza-
ble)
At "0" to "1" and at "1"
to "0"
Input characteristic
Connection of two-wire
BEROs
S
Permissible
closed-circuit current
Please note the total current per ET 200X.
detection is 0.6 mA
I
1.5 mA
<
<
4
Up to 40 _C
max. 0.5A;
Up to 55 _C
max. 0.4A
Up to 40 _C
max. 0.9A;
Up to 55 _C
max. 0.7A
Yes, electronic
24 VDC
13 to 30 V
– 3 to 5 V
Typ. 10 mA
Typ. 0.5 ms
Typ. 3 ms
Typ. 15 ms
Typ. 20 ms
To IEC 61131, Type 2
Possible
Max. 1.5 mA **
7-43