Pinout Of The Coupler Plugs For Digital Outputs When A Y Connector Is Used - Siemens SIMATIC ET 200X Manual

Distributed i/o device
Table of Contents

Advertisement

Wiring of coupler plugs (DO) for Y connector
To connect the digital outputs using a Y connector, you require:
S A Y connector
S Two M12 coupler plugs
S A flexible, 3- or 4-core copper cable with a core cross-section of v 0.75 mm
Wire the two M12 coupler plugs for the Y connector in accordance with the pinout
table below. The assignment of pin 4 depends on the socket of the ET 200X to
which you screw the Y connector.
Table 4-12 Pinout of the coupler plugs for digital outputs when a Y connector is used
Pin
1
2
3
Chassis ground, load voltage
4
Output signal on
socket X1: channel 0
socket X2: channel 1
socket X3: channel 2
socket X4: channel 3
5
PE
Pinout of the sockets for inputs/outputs
The pinout of the sockets for inputs/outputs is shown together with the data for the
individual modules in Section 7.1 ff.
Wiring the M12 coupler plug for analog inputs and outputs
To connect the analog inputs and analog outputs, you require:
S A 4- or 5-pin, M12 coupler plug
S A shielded 4-core copper cable with a core cross-section of v 0.75 mm
Wire the coupler plug in accordance with the pinout of the sockets on the
expansion module. You will find the pinout in the information on the various
modules as of Section 7.21.9. You may have to connect the expansion module to
the protective ground (see Section 4.4.6).
ET 200X Distributed I/O Device
EWA 4NEB 780601602-06
Coupler plug assignment ...
A (top)
B (bottom)
Output signal on
socket X1: channel 1
socket X2: –
socket X3: channel 3
socket X4: –
Wiring
2
View of
Y connector
A
A
4
(top)
(top)
3
5
1
2
2
1
5
3
B
4
(bottom)
2
4-29