Table 31. General unit alarming
Emergency Stop (In Alarm)
Notification Class
Unit will shut down and be
prevented from operating
HVAC Critical Alarm.
until the sensor is in a
normal state.
External Auto/Stop (In Alarm)
Notification Class
Unit will shut down and be
prevented from operating
HVAC Critical Alarm.
until the sensor is in a
normal state.
Local Auto/Stop (In Alarm)
Notification Class
Unit will shut down and be
prevented from operating
HVAC Critical Alarm.
until the sensor is in a
normal state.
Discharge Air Temperature (In Fault)
Notification Class
Unit will shut down and be
prevented from running
HVAC Critical Alarm.
until this sensor is in a
normal state.
PKG-SVX027A-EN
Action
Reason
The emergency stop input
has an open condition which
indicates an emergency stop
command.
Action
Reason
Theexternal auto/stop input
has an open condition which
indicates an emergency stop
command.
Action
Reason
The local auto/stop value
has been commanded to the
local stop command.
Action
Reason
The temperature sensor is
reading either above is
maximum value or below is
minimum value, resulting in
a Fault Condition after 3
point updates.
Typical Causes
Manual reset required once
• Emergency Stop Binary
Input is open.
the issue is resolved. User
must toggle the alarm reset
value.
Typical Causes
• Emergency stop binary
input is open.
None, alarm clears once
sensor is in a normal state.
Typical Causes
• Emergency stop binary
input is open.
None, alarm clears once
sensor is in a normal state.
Typical Causes
• Sensor is not wired
properly: Verify sensor
wiring to the XM Module.
• XM Module is not
communicating. Ensure that
None, alarm clears once
the XM Module is up and
talking to the UC600.
sensor is in a normal state.
• Sensor has Failed. Verify if
sensor has any resistance
on it, should be 8-12k of
resistance on the
thermistor.
Diagnostics
Reset Required
Reset Required
Reset Required
Reset Required
77