Trane SCWM Series Installation, Operation And Maintenance Manual page 11

Modular self-contained 40 to 80 tons
Table of Contents

Advertisement

Table 2.
SCWM EER/IEER ratings (continued)
Tonnage
Model No.
SCWMN05LF
SCWMN050F
50
SCWMN05L4
SCWMN0504
SCWMN06LF
SCWMN060F
60
SCWMN06L4
SCWMN0604
SCWMN07LF
SCWMN070F
70
SCWMN07L4
SCWMN0704
SCWMN08LF
SCWMN080F
80
SCWMN08L4
SCWMN0804
Notes:
1. Cooling Only.
2. Cooling performance is rated at 80F EDB/67F EWB with 85 EWT for water-cooled performance and 95F Ambient for air-cooled
performance.
3. EER, IEER, and AHRI Net Cooling Capacity are tested in accordance with the AHRI 340/360 (I-P) and certified to 10 CFR Part 431 from
the US Department of Energy.
Table 3.
SCWM water volumes
Tonnage
Gallons
40 Ton
8.2
50 Ton
9.7
60 Ton
9.7
70 Ton
12.9
80 Ton
12.9
PKG-SVX027A-EN
EER
15.8
14.9
15.8
14.9
15.7
14.8
15.7
14.8
15.8
14.9
15.8
14.9
15.7
14.7
15.7
14.7
Water Volume in U.S. Gallons/Liters
w/o Economizer
Liters
31.0
36.7
36.7
48.9
48.9
AHRI Net Cooling Capacity
IEER (VAV)
19.5
19.5
19.5
19.5
18.5
18.5
18.5
18.5
19.5
19.5
19.5
19.5
20.8
20.8
20.8
20.8
With Chem. Cleanable Econ, Add
Gallons
12.0
14.4
19.1
24.0
24.0
General Data
(BTUH)
540
600
540
600
636
696
636
696
780
840
780
840
876
936
876
936
Liters
45.4
54.5
72.3
90.8
90.8