Trane SCWM Series Installation, Operation And Maintenance Manual page 46

Modular self-contained 40 to 80 tons
Table of Contents

Advertisement

Operating Principles
High Pressure Limit conditions can be caused by the
following:
low condenser water flow
high entering condenser water temperature
fouled entering condenser water strainer
TXV malfunction
refrigerant over charge
water regulating valve (WRV) malfunction
faulty discharge pressure sensor
Figure 37. Fixed Speed Compressor Protection Module (MCSP)
46
The Unit Controller's TD7 will annunciate a Limit
Condition if an FS compressor circuit enters one. If the unit
is equipped with WRV, the Unit Controller can open the
valve to allow more flow through the condenser to help
mitigate an HPC trip.
If the VS circuit enters either a High or Low Pressure limit
condition the Unit Controller can reduce compressor
speed to help mitigate either a Low or High pressure
diagnostic trip.
PKG-SVX027A-EN