Selection Procedures; Determination Of Minimum Circuit Ampacity (Mca) - Trane SCWM Series Installation, Operation And Maintenance Manual

Modular self-contained 40 to 80 tons
Table of Contents

Advertisement

Selection Procedures

RLA = Rated Load Amps
Compressor LRA = Locked Rotor Amps
Compressor Input = VFD drive Input

Determination of Minimum Circuit Ampacity (MCA)

MCA = 1.25 x Largest motor amps/VFD Input + the sum of
the remaining motor amps.
Determination of Max Fuse (MFS) and Max
Circuit Breaker (MCB) sizes
MFS and MCB = 2.25 x Largest motor amps (RLA)/VFD
input) + the sum of the remaining motor amps.
Number of compressors
Table 14.
SCWMN
MSC
04L
66cc - ZPV0662
1
96cc - ZPV0962
0
ZP154KCE-TE
0
ZP181KCE-TE
1
Table 15. Number of fans/unit
MSC
Fans
*40-50 qty(4) fans optional
*70-80 qty(6) fans optional
Table 16. Compressor electrical data
ZP181KCE-TE
15 Ton
96CC-ZPV0962 (vfd)
Table 17. Fan motor electrical data
Drive (K3G500) - Motor (M3G150-IF)
PKG-SVX027A-EN
SCWMN
SCWMN
SCWMN
040
05L
050
0
1
0
1
0
1
0
2
2
1
0
0
40 Ton
3
200
RLA
LRA
55.77
340
-
Compressor Output = VFD drive output
Voltage utilization range is ±10%
If the rating value calculation does not equal a standard
over current protective device rating, use the next lower
standard rating as the maximum.
SCWMN
SCWMN
06L
060
1
0
0
1
0
0
2
2
50 Ton
60 Ton
3
4
460
RLA
LRA
23.77
110
-
-
-
Installation - Electrical
SCWMN
SCWMN
SCWMN
07L
070
08L
1
0
0
1
3
3
0
0
70 Ton
5
200
INPUT
OUTPUT
INPUT
-
-
-
56
58
30
200
INPUT
18.6
SCWMN
080
1
0
0
1
0
0
3
3
80 Ton
5
460
OUTPUT
-
31
460
INPUT
9
37