Diagnostics
Table 28. Compressor alarming (continued)
Diagnostic: Compressor (1-4) High Pressure Shutdown (In Alarm)
Notification Class
Compressor will be locked
out and prevented from
HVAC Critical Alarm.
running until this diagnostic
is cleared.
Compressor (1-4) High Pressure Cutout (In Alarm)
Notification Class
The High Pressure cutout
HVAC Critical Alarm.
switch is reading a ciosed
condition which indicates
Diagnostic: Compressor (1-4) Frostat (In Alarm)
Notification Class
Compressor will be locked
out and prevented from
HVAC Critical Alarm.
running until this diagnostic
is cleared.
Diagnostic: Compressor (1-4) High Superheat (In Alarm)
Notification Class
Compressor will be locked
out and prevented from
HVAC Critical Alarm.
running until this diagnostic
is cleared.
74
Action
Reason
The temperature sensor is
reading either above is
maximum value or below is
minimum value, resulting in
an Alarm Condition after 3
point updates.
Action
Reason
The temperature sensor is
reading either above is
maximum value or below is
minimum value, resulting in
an Alarm Condition after 3
point updates.
Action
Reason
The Calculated Saturated
Suction Refrigerant
Temperature is below 32
degrees for 5 minutes.
Action
Reason
The Calculated superheat is
above 25 degrees for 10
minutes.
Typical Causes
• Sensor is not wired
properly: Verify sensor
wiring to the XM Module.
• XM Module is not
Manual Reset Required once
communicating. Ensure that
the sensor is in a Normal
the XM Module is up and
State. User must toggle the
talking to the UC600.
• Discharge Pressure is too
Compressor (1-4) Failure
high and over the cutout
Reset
threshold of the High
Pressure Switch. Verify
Condenser Pressure.
• Cutout Switch has failed.
Typical Causes
• Sensor is not wired
properly: Verify sensor
wiring to the XM Module.
• XM Module is not
communicating. Ensure that
the XM Module is up and
None, alarm clears once
talking to the UC600.
sensor is in a normal state.
• Discharge Pressure is too
high and over the cutout
threshold of the High
Pressure Switch. Verify
Condenser Pressure.
• Cutout Switch has failed.
Typical Causes
• Low Airflow across the
Manual Reset Required once
Evaptorator.
the issue is resolved. User
• Partially blocked Evaporator.
must toggle the Compressor
• Dirty Air Filter
(1-4) Failure Reset.
• Dirty Evaporator Coil
Typical Causes
• Low Charge on unit.
Manual Reset Required once
• Malfunctioning TXV.
the issue is resolved. User
• Too High of a heat load
must toggle the Compressor
• Too much air across the
(1-4) Failure Reset
evaporator
Reset Required
Reset Required
Reset Required
Reset Required
PKG-SVX027A-EN