Table 23. Points list (continued)
Hardware
Connection
AO1/UI1
AO2/UI2
XM30.9
AO3/UI3
AO4/UI4
AO1/UI1
AO2/UI2
XM30.10
AO3/UI3
AO4/UI4
AO1/UI1
AO2/UI2
XM30.11
AO3/UI3
AO4/UI4
BO1
BO2
XM32.12
BO3
BO4
BO1
BO2
XM32.13
BO3
BO4
AO1/UI1
AO2/UI2
XM30.14
AO3/UI3
AO4/UI4
AO1/UI1
AO2/UI2
XM30.15
AO3/UI3
AO4/UI4
PKG-SVX027A-EN
Point Name
Compressor 2 Discharge Pressure Sensor Local
Compressor 2 Suction Pressure
Compressor 2 Suction Temperature
Compressor 2 Condenser Regulating Valve
Compressor 3 Discharge Pressure Sensor Local
Compressor 3 Suction Pressure
Compressor 3 Suction Temperature
Compressor 3 Condenser Regulating Valve
Compressor 4 Discharge Pressure Sensor Local
Compressor 4 Suction Pressure
Compressor 4 Suction Temperature
Compressor 4 Condenser Regulating Valve
Cooling Tower/Pump Request
Unit Alarm Output Command
VAV Box Drive Open Command
Comp 1 VFD E-Stop Alarm Contact
Dirty Filter Alarm
Refrigeration Circuit Failure Alarm
Supply Fan Failure Alarm
Heat Failure Alarm
Occupied Zone Cool Setpoint
Occupied Zone Heat Setpoint
Unoccupied Zone Cool Setpoint
Unoccupied Zone Heat Setpoint
Supply Air Cooling Setpoint
Supply Air Heating Setpoint
Supply Air Static Pressure Setpoint
Demand Limit Input
Point Setup
0.5VDC = 0 PSI, 4.5VDC = 667 PSI
0.5VDC = 0 PSI, 4.5VDC = 667 PSI
10K Ohm Resistor Trane Type 2
2VDC = 0% Open, 10VDC = 100% Open
0.5VDC = 0 PSI, 4.5VDC = 667 PSI
0.5VDC = 0 PSI, 4.5VDC = 667 PSI
10K Ohm Resistor Trane Type 2
2VDC = 0% Open, 10VDC = 100% Open
0.5VDC = 0 PSI, 4.5VDC = 667 PSI
0.5VDC = 0 PSI, 4.5VDC = 667 PSI
10K Ohm Resistor Trane Type 2
2VDC = 0 % Open, 10VDC = 100% Open
NO Open = Request for Off, NO Closed = Request for On;
NC Not Used
NO Open = No Alarm, NO Closed = Alarm;NC not used
NO Open = Normal Operation, NO Closed = Drive Max
Valve Position; NC Not used
NO Open = Normal, NO Closed = Emergency Stop, NC
Not used
NO Open = Normal, NO Closed = Alarm; NC Not used
Open = Normal, Closed = Alarm
Open = Normal, Closed = Alarm
Open = Normal, Closed = Alarm
0.5VDC = 50 Deg F, 4.5VDC = 90 Deg F
0.5VDC = 50 Deg F, 4.5VDC = 90 Deg F
0.5VDC = 50 Deg F, 4.5VDC = 90 Deg F
0.5VDC = 50 Deg F, 4.5VDC = 90 Deg F
0.5VDC = 40 Deg F, 4.5VDC = 90 Deg F
0.5VDC = 40 Deg F, 4.5VDC = 90 Deg F
0.5VDC = 0 In WC, 4.5VDC = 5 In WC
Open = Normal, Closed = 50% Reduction
NO = Normally Open, NC = Normally Closed