Wiring Burglary, Panic and Smoke Detector Devices to Zones 1-9

The maximum zone resistance is 100 ohms for
zones 1 and 8, and 300 ohms for all other
zones (excluding the 2K EOL resistor).
To wire burglary and panic devices to zones 1-9, connect
sensors/contacts to the hardwire zone terminals (10
through 23). See Figure 3-9. Connect N.C. and N.O.
devices as follows:
3-6
Handset
26
27

Figure 3-8: Telephone Line Connections

Red Jumper
ZONE 2 ZONE 3
10
11
12
13
14
15
ZONE 1
+
+
-
N.C.
N.C.
N.O.
N.O.
2k EOLR
2k EOLR
+
+
-
Fire
Usage
N.C.
SMOKE
N.O.
N.C.
Burg.
Usage
2k EOLR
N.O.
Zone resistance (Excluding EOLR):
ZONE 1,8: 100 OHMS MAXIMUM
2k EOLR
ALL OTHER ZONES: 300 OHMS MAXIMUM

Figure 3-9: Wiring Connections for Zones 1-9

Incoming
Telco Line
28
29
30
EARTH GROUND
DIRECT
CONNECT
CORD
RJ31X
JACK
PLUG
Connect N.C. devices in series with the high (+)
side of the loop. The 2K EOL resistor must be
connected in series with the devices, following the
last device.
Connect N.O. devices in parallel (across) the loop.
The 2K EOL resistor must be connected across the
loop wires at the last device.
ZONE 4 ZONE 5
ZONE 6 ZONE 7
16
17
18
19
20
+
+
-
N.C.
N.C.
N.O.
N.O.
2k EOLR
2k EOLR
+
-
N.C.
N.O.
2k EOLR
2k EOLR
Zone response time:
ZONES 1-8: 350mSec-500mSec
ZONE 9: Programmable for
INCOMING TELCO LINE
TIP
PREMISES
RING
PHONES
ZONE 8 ZONE 9
21
22
23
+
-
+
GLASS
BREAK
N.C.
N.C.
N.C.
N.O.
Fast: 10mSec-15mSec
Normal: 350mSec-500mSec
(default response)