VISTA-40 Installation and Setup Guide
TERMINALS
ON CONTROL
Wiring Burglary, Panic and Smoke Detector Devices to Zones 1-9
The maximum zone resistance is 100 ohms for
zones 1 and 8, and 300 ohms for all other
zones (excluding the 2K EOL resistor).
To wire burglary and panic devices to zones 1-9, connect
sensors/contacts to the hardwire zone terminals (10
through 23). See Figure 3-9. Connect N.C. and N.O.
devices as follows:
3-6
Handset
26
27
Figure 3-8: Telephone Line Connections
Red Jumper
ZONE 2 ZONE 3
10
11
12
13
14
15
ZONE 1
+
+
-
N.C.
N.C.
N.O.
N.O.
2k EOLR
2k EOLR
+
+
-
Fire
Usage
N.C.
SMOKE
N.O.
N.C.
Burg.
Usage
2k EOLR
N.O.
Zone resistance (Excluding EOLR):
ZONE 1,8: 100 OHMS MAXIMUM
2k EOLR
ALL OTHER ZONES: 300 OHMS MAXIMUM
Figure 3-9: Wiring Connections for Zones 1-9
Incoming
Telco Line
28
29
30
EARTH GROUND
DIRECT
CONNECT
CORD
RJ31X
JACK
PLUG
•
Connect N.C. devices in series with the high (+)
side of the loop. The 2K EOL resistor must be
connected in series with the devices, following the
last device.
•
Connect N.O. devices in parallel (across) the loop.
The 2K EOL resistor must be connected across the
loop wires at the last device.
ZONE 4 ZONE 5
ZONE 6 ZONE 7
16
17
18
19
20
+
+
-
N.C.
N.C.
N.O.
N.O.
2k EOLR
2k EOLR
+
-
N.C.
N.O.
2k EOLR
2k EOLR
Zone response time:
ZONES 1-8: 350mSec-500mSec
ZONE 9: Programmable for
INCOMING TELCO LINE
TIP
PREMISES
RING
PHONES
ZONE 8 ZONE 9
21
22
23
+
-
+
GLASS
BREAK
N.C.
N.C.
N.C.
N.O.
Fast: 10mSec-15mSec
Normal: 350mSec-500mSec
(default response)