Checking The Motor Protection Switches; Completion Of Electrical Work - Kessel Aqualift F Installation Manual

Pumping station for all wastewaters (with / without sewage) for underground / sub-surface installation
Table of Contents

Advertisement

Connection
Battery connection
Power connection
Motor / pump cables
Motor temperature sensors
Float switch connections
Warning and Alarm outputs
5.6 Controls

Checking the motor protection switches

The motor protection switch must be set for the
appropriate rated current of the pumps – as descri-
bed in Section 3 of this manual
5. Electrical Connections
Double Pump Systems – Follow all safety regulations!
Instructions
• both 9-volt batteries located inside the control unit must be connected.
• Power cables L1, L2, L3, N and PE should be connected to their appropriate jacks.
• It is mandatory that cables N and PE are connected and connected properly.
• The power supply cable to the control unit must be equipped with a main On / Off switch
• Each phase of the main power cable must be equipped with a fuse with a max rating
of 16 Amps
• Improper cable connection (Phase and N reversed) will cause the internal fuse (315
mAT) to blow.
• The 2 x motor / pump cables U/V/W should be connected to the T1 / T2 / T3 connection
jacks. Pump 1 connections are on the left, Pump 2 connections are on the right.
• The PE cable is to be connected to the TF1 and TF2 jacks on the connection block lo-
cated below the motor protection switch. Pump 1 connections are on the left, Pump 2
connections are on the right.
• Pump 1 and Pump 2
• Cable number 4 on the motor supply cable should be connected to lowest jack on the
TF2 TF1 connection area.
• Cable 5 on the motor supply cable should be connected to the middle jack on the TF2
TF1 connection area.
• Cable 6 on the motor supply cable should be connected to the top jack on the TF2 TF1
connection area. The 2 polar 'bridge' must be removed if present.
The cable ends of the float switches are to be connected to the appropriate connec-
tion jacks in the HAZARD area inside the control unit which are protected by the elec-
trical shield.
• The 'Störung' (malfunction) and 'Alarm' (alarm) control unit signals are controlled by a
relay. Inductive loads must be externally eliminated. The stand by (powerless) position
of the relays is printed on the board. This means the 'Warning' and 'Alarm' signals are
activated.
• 42 V ac dc / 0,5 A

5.7 Completion of electrical work

After all electrical connection work has been completed in the
control unit, the control unit cover must be closed and pro-
perly secured. In order to eliminate odour nuisances in the
area where the control unit is installed, the conduit pipe to the
control unit should be sealed with a special gaskets or sim-
ply with insulation foam.