Kessel Aqualift F Installation Manual page 7

Pumping station for all wastewaters (with / without sewage) for underground / sub-surface installation
Table of Contents

Advertisement

3.1 Explosion proof pumps according to ATEX
Type
Rated input (P1)
Rated output (P2)
Operating voltage
Frequency
Current
Fusing
Protection Class
Pump cable length
Allowable wastewater temp.
Max running time at 40 deg C
Pump weights
Classifications:
• Operating modes: Pump submerged – Continuous operation S1
• Pumps with the TPF . . . ex identification according to Unit Group II, Unit Category 2G (Explosion endangered
areas Zone 1 and 2) are designed for installation in atmospheres containing dangerous gases which require the
Explosion Group IIB and the Temperature Class T4. Pumps constructed according to this designation comply with
the ignition protection type 'pressure protection encapsuled'.
Performance Curve
35
30
25
20
15
10
5
0
0
0
3. Technical Data
1,75 kW
TPF 1,3
1,3 kW
3,56 A
10 m Länge, 7 x 1,5 mm
II 2G Ex d IIB T4 LCIE 06 ATEX 6043X
0081
Q
according to DIN 1986 (v
min
for DN 50
TPF 1,3 kW
5
10
1
2
7
400 V DS
3 x 16 A träge
2
640 minutes (see settings in chapter 5.7)
39 kg
= 0,7m/s)
min
for DN 80
TPF 1,9 kW
15
3
4
TPF 1,9
50 Hz
IP 68
10 m Length 7 x 1,5 mm
40 °C
20
Flow Q
(cubic meters / hour)
5
(liters / second)
2,6 kW
1,9 kW
4,5 A
2
39 kg
EX

Advertisement

Table of Contents
loading

This manual is also suitable for:

Aqualift f duo