Frequency setting by analog input (terminal 1, 2, 4)
Forward
STF
rotation
PC
0 to 5VDC
10
Frequency
2
setting
5
Connection diagram using
terminal 2 (0 to 5VDC)
Forward
STF
rotation
PC
0 to 10VDC
10E
Frequency
2
setting
5
Connection diagram
using terminal 2 (0 to 10VDC)
Forward
rotation
STF
Terminal 4
AU
input selection
PC
DC0 to 5V
10
Frequency
4
setting
5
Connection diagram
using terminal 4 (0 to 5VDC)
Forward
rotation
4 to 20mADC
Current
Frequency
input
setting
equipment
Connection diagram using
terminal 4 (4 to 20mADC)
Forward
rotation
4 to 20mADC
Current
Frequency
input
setting
equipment
Connection diagram using
terminal 2 (4 to 20mADC)
168
(2) Perform operation by analog input voltage
 The frequency setting signal inputs 0 to 5VDC (or 0 to 10VDC) to across
Inverter
Voltage/current
the terminals 2 and 5. The 5V (10V) input is the maximum output
input switch
frequency. The maximum output frequency is reached when 5V (10V) is
4
2
input.
 The power supply 5V (10V) can be input by either using the internal
power supply or preparing an external power supply. The internal power
supply outputs 5VDC across terminals 10 and 5, or 10V across terminals
10E and 5.
Terminal
Inverter
Voltage/current
10
input switch
4
2
10E
 When inputting 10VDC to the terminal 2, set any of "0, 2, 4, 10, 12, 14"
in Pr. 73. (The initial value is 0 to 5V)
 Setting "1 (0 to 5VDC)" or "2 (0 to 10VDC)" in Pr. 267 changes the
terminal 4 to the voltage input specification. When the AU signal turns
Inverter
ON, the terminal 4 input becomes valid.
Voltage/current
input switch
REMARKS
4
2
The wiring length of the terminal 10, 2, 5 should be 30m maximum.
(3) Perform operation by analog input current
Inverter
 When the pressure or temperature is controlled constant by a fan, pump,
STF
etc., automatic operation can be performed by inputting the output signal
Voltage/current
AU
4 to 20mADC of the adjuster to across the terminals 4 and 5.
input switch
PC
 The AU signal must be turned ON to use the terminal 4.
4
2
4
5
 Setting any of "6, 7, 16, 17" in Pr. 73 changes the terminal 2 to the
Inverter
current input specification. At this time, the AU signal need not be turned
STF
Voltage/current
ON.
input switch
PC
4
2
2
5
Inverter Built-in Power
Frequency Setting
Supply Voltage
5VDC
10VDC
Pr. 73 (terminal 2
Resolution
input voltage)
0.024/50Hz
0 to 5VDC input
0.012/50Hz
0 to 10VDC input