Mitsubishi F700 Series Instruction Manual page 283

Hide thumbs Also See for F700 Series:
Table of Contents

Advertisement

PID control
Pre-charge operation
 When the measured amount reaches the pre-charge ending level
Measured value[PSI]
Pr.761
Ending level
Output frequency[Hz]
Pr.127
0 Hz
STF
Output signal
Pre-charge
Y49
 When the elapsed time reaches the pre-charge ending time
Output frequency[Hz]
Pr.127
Ending time
Pr.762
0 Hz
STF
Output
Pre-charge
signal
Y49
 When the signal is input to end the pre-charge operation
Output frequency[Hz]
Pr.127
0 Hz
STF
Pre-charge end
command
X77
Output signal
Pre-charge
Y49
272
PID control
PID control
Time
PID control
Time
20ms or more
When the measured amount reaches the Pr. 761
Time
setting or higher, the pre-charge operation
ends, and PID control starts.
Pr. 761 Pre-charge ending level
Time
When the pre-charging time reaches the Pr. 762
setting or higher, the pre-charge operation
ends, and PID control starts.
Pr. 761 Pre-charge ending level
Pr. 762 Pre-charge ending time
When the X77 signal turns ON, the pre-charge
operation ends, and the PID control starts.
(If a start command is given while the X77
signal is ON, the pre-charge operation is not
performed, and PID control is performed from
the beginning. )
Pr. 178 to Pr. 189
X77 assigned
REMARKS
 If the X77 signal stays ON, the pre-charge
operation is not performed after the PID
output suspension (SLEEP). To enable the
X77 signal function after the PID output
suspension (SLEEP), confirm the during pre-
charge operation signal (Y49) = OFF, and
turn OFF the X77 signal.
 To perform PID control immediately after the
PID output suspension (SLEEP), keep the
X77 signal ON until the PID control ends.
9999
9999
9999