Bias And Gain Of Frequency Setting Voltage (Current) (Pr. 125, Pr. 126, Pr. 241, C2(Pr. 902) To C7(Pr. 905)) - Mitsubishi F700 Series Instruction Manual

Hide thumbs Also See for F700 Series:
Table of Contents

Advertisement

Frequency setting by analog input (terminal 1, 2, 4)
4.16.4 Bias and gain of frequency setting voltage (current)
(Pr. 125, Pr. 126, Pr. 241, C2(Pr. 902) to C7(Pr. 905))
You can set the magnitude (slope) of the output frequency as desired in relation to the frequency setting signal (0
to 5V, 0 to 10V or 4 to 20mADC).
Set Pr. 73 and Pr. 267 to switch between 0 to 5VDC, 0 to 10VDC and 4 to 20mADC. (Refer to page 166)
Parameter
Number
Terminal 2 frequency setting gain
125
frequency
Terminal 4 frequency setting gain
126
frequency
Analog input display unit
241
*1, 3
switchover
Terminal 2 frequency setting bias
C2(902)
*1, 2
frequency
Terminal 2 frequency setting bias
C3(902)
*1, 2
C4(903)
Terminal 2 frequency setting gain
*1, 2
Terminal 4 frequency setting bias
C5(904)
*1, 2
frequency
C6(904)
Terminal 4 frequency setting bias
*1, 2
C7(905)
Terminal 4 frequency setting gain
*1, 2
*1
The parameters can be set when Pr. 160 User group read selection = "0". (Refer to page 185.)
*2
The parameter number in parentheses is the one for use with the parameter unit (FR-PU04/FR-PU07).
*3
The above parameters allow its setting to be changed during operation in any operation mode even if "0" (initial value) is set in Pr. 77 Parameter
write selection.
172
Name
Initial Value
Setting
Range
Set the frequency of terminal 2 input gain
50Hz
0 to 400Hz
(maximum).
Set the frequency of terminal 4 input gain
50Hz
0 to 400Hz
(maximum).
0
Displayed in %
0
1
Displayed in V/mA
Set the frequency on the bias side of
0Hz
0 to 400Hz
terminal 2 input.
Set the converted % of the bias side
0%
0 to 300%
voltage (current) of terminal 2 input.
Set the converted % of the gain side
100%
0 to 300%
voltage (current) of terminal 2 input.
Set the frequency on the bias side of
0Hz
0 to 400Hz
terminal 4 input.
Set the converted % of the bias side
20%
0 to 300%
current (voltage) of terminal 4 input.
Set the converted % of the gain side
100%
0 to 300%
current (voltage) of terminal 4 input.
Description
Select the unit of
analog input display.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents