ANALOG VALUE
Object
Object Name
Identifier
1
Output frequency
2
Output current
3
Output voltage
6
Running speed
Converter output
8
voltage
14
Output power
17
Load meter
Cumulative
20
energization time
23
Actual operation time
25
Cumulative power
52
PID set point
54
PID deviation
67
PID measured value 2
200
Alarm history 1
201
Alarm history 2
202
Alarm history 3
203
Alarm history 4
300
Speed scale
*2
310
PID set point CMD
PID measured value
311
CMD
*2
312
PID deviation CMD
398
Mailbox parameter
399
Mailbox value
10007
Acceleration time
10008
Deceleration time
*1
R: Read only
W: Read/Write (Commandable values not supported)
*2
If communication speed command source is except for NET, the setting value can be written, but not to be applied.
When both C42 (Pr. 934 ) and C44 (Pr. 935 ) "9999", setting range is smaller coefficient to larger coefficient of C42 (Pr. 934 ) and C44 (Pr. 935 ).
*3
Depending on a value, the writing value and the reading value may not be same at the minimum digit.
Present Value
Access Type
*1
R
Represents the output frequency monitor.
R
Represents the output current monitor.
R
Represents the output voltage monitor.
R
Represents the running speed monitor.
R
Represents the converter output voltage monitor.
R
Represents the output power monitor.
R
Represents the load meter monitor.
Represents the cumulative energization time
R
monitor.
R
Represents the actual operation time monitor.
R
Represents the cumulative power monitor.
R
Represents the PID set point monitor.
Represents the PID deviation monitor.
R
(minus display is available with reference to 0%,
0.1% increment)
R
Represents the PID measured value 2 monitor.
Represents the fault history 1 (the latest fault)
R
monitor.
Represents the fault history 2 (second fault in past)
R
monitor.
Represents the fault history 3 (third fault in past)
R
monitor.
Represents the fault history 4 (fourth fault in past)
R
monitor.
Controls the ratio to the frequency command.
C
(Setting range: 0.00 to 100.00)
(Refer to page 244)
Controls the PID set point.
This object is the PID set point during PID operation
C
*2
if Pr. 128 (Pr. 753) = "60 or 61"
(Setting range: 0.00 to 100.00)
Controls the PID measured value.
This object is the PID measured value during PID
C
operation if Pr. 128 (Pr. 753) = "60 or 61"
(Setting range: 0.00 to 100.00)
Controls the PID deviation.
This object is the PID deviation during PID operation
C
*2
if Pr. 128 (Pr. 753) = "50 or 51"
(Setting range: -100.00 to 100.00)
W
Access to the properties which are not defined as
objects are available. (Refer to page 250)
W
W
Sets Pr.7 Acceleration time
W
Sets Pr.8 Deceleration time
Communication operation and setting
Description
*3
*3
C: Read/Write (Commandable values supported)
Unit
hertz (27)
amperes (3)
volts (5)
revolution-per-
minute
(104)
volts (5)
kilowatts (48)
percent (98)
hours (71)
hours (71)
kilowatt-hours (19)
no-units (95)
no-units (95)
no-units (95)
no-units (95)
no-units (95)
no-units (95)
no-units (95)
percent (98)
no-units (95)
no-units (95)
percent (98)
4
no-units (95)
no-units (95)
seconds (73)
seconds (73)
247