Parameter Copy And Parameter Verification; Parameter Copy - Mitsubishi F700 Series Instruction Manual

Hide thumbs Also See for F700 Series:
Table of Contents

Advertisement

4.27 Parameter copy and parameter verification

PCPY Setting
0
1
2
3
REMARKS
· When the copy destination inverter is not the FR-F700 series or parameter copy write is performed after parameter copy read is
stopped, "model error (
· Refer to the parameter list on
· When the power is turned OFF or an operation panel is disconnected, etc. during parameter copy write, perform write again or check the
values by parameter verification.
· Initial settings of certain parameters are different for different capacities, so some parameter settings may be automatically
changed when parameter copy is performed from a different-capacity inverter. After performing a parameter copy from a
different-capacity inverter, check the parameter settings. (Refer to the parameter list (page
initial settings for different capacities.)
· If parameters are copied to the inverter with additional parameters (version up model) from the inverter without additional
parameters, a value out of the setting range may be written to the inverter. In this case the inverter operates as if the initial value
is written to the parameter.

4.27.1 Parameter copy

Parameter settings can be copied to multiple inverters.
Operation
1.
Connect the operation panel to the
copy source inverter.
• Connect it during a stop.
2.
Press
to choose the parameter
setting mode.
3.
Turn
until
appears.
4.
Press
to to read the present set value.
"
"(initial value) appears.
5.
Turn
to change it to
the setting value " ".
6.
Press
to copy the source parameters
to the operation panel.
7.
Connect the operation panel to the
copy destination inverter.
8.
After performing steps 2 to 5,
turn
to change it to "
9.
Press
to write the parameters copied to
the operation panel to the destination inverter.
10.
When copy is completed,
"
" and "
11.
After writing the parameter values to the copy
destination inverter, always reset the inverter,
e.g. switch power OFF once, before starting operation.
Cancel
Copy the source parameters to the operation panel.
Write the parameters copied to the operation panel into the destination inverter.
Verify parameters in the inverter and operation panel. (Refer to page 322.)
)" is displayed.
page
384 and later for availability of parameter copy.
(parameter copy)
About 30s later
".
" flicker.
Parameter copy and parameter verification
Description
) for the parameters with different
56
Display
The parameter
number previously
read appears.
The frequency flickers
Flicker ··· Parameter copy complete!!
The frequency flickers
for about 30s
Flicker ··· Parameter copy complete!!
for about 30s
321
4