Analog Input - Mitsubishi F700 Series Instruction Manual

Hide thumbs Also See for F700 Series:
Table of Contents

Advertisement

Communication operation and setting
(6) Supported BACnet object

ANALOG INPUT

Object
Object Name
Identifier
0
Terminal 1
1
Terminal 2
2
Terminal 4
*1
R: Read only
W: Read/Write (Commandable values not supported)
ANALOG OUTPUT
Object
Object Name
Identifier
0
Terminal CA
1
Terminal AM
*1
R: Read only
W: Read/Write (Commandable values not supported)
*2
Available regardless of the operation mode, operation command source and speed command source.
246
Present Value
Access Type
*1
Represents actual input voltage of terminal 1.
(The range varies depending on the Pr. 73 and Pr. 267 settings.
R
Represents actual input voltage (or input current) of terminal 2.
(The range varies depending on the Pr. 73 and Pr. 267 settings.
R
Represents actual input voltage (or input current) of terminal 4.
(The range varies depending on the Pr. 73 and Pr. 267 settings.
R
Present Value
Access Type
*1
Controls actual output current level of terminal CA.
Control is available when Pr. 54 CA terminal function selection =
C
"85"
*2
.
(Setting range: 0.0% to 100.0% (0 to 20mA))
Controls actual output voltage level of terminal AM.
Control is available when Pr. 158 AM terminal function selection =
C
"86"
*2
.
(Setting range: 0.0% to 100.0% (0 to 10V))
Description
-10 to +10V (-100% to +100%),
-5 to +5V (-100% to +100%) )
0 to 10V (0% to 100%),
0 to 5V (0% to 100%),
0 to 20mA (0% to 100%) )
2 to 10V (0% to 100%),
1 to 5V (0% to 100%),
4 to 20mA (0% to 100%) )
C: Read/Write (Commandable values supported)
Description
C: Read/Write (Commandable values supported)
Unit
percent
(98)
percent
(98)
percent
(98)
Unit
percent
(98)
percent
(98)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents