Mitsubishi F700 Series Instruction Manual page 240

Hide thumbs Also See for F700 Series:
Table of Contents

Advertisement

(3) Message format
Programmable controller (Master)
Programmable controller (Master)
Data check time
Item
Various monitors, operation command,
frequency setting (RAM)
Parameter read/write, frequency
setting (EEPROM)
Parameter clear/all clear
Reset command
1) Query
The master sends a message to the slave (= inverter) at the specified address.
2) Normal Response
After receiving the query from the master, the slave executes the requested function and returns the corresponding
normal response to the master.
3) Error Response
If an invalid function code, address or data is received, the slave returns it to the master.
When a response description is returned, the error code indicating that the request from the master cannot be
executed is added.
No response is returned for the hardware-detected error, frame error and CRC check error.
4) Broadcast
By specifying address 0, the master can send a message to all slaves. All slaves that received the message from the
master execute the requested function. In this communication, the slaves do not return a response to the master.
REMARKS
The slave executes the function independently of the inverter station number setting (Pr. 331) during broadcast communication.
Query communication
Query Message
Inverter (slave)
Broadcast communication
Query Message
Inverter (slave)
Check Time
< 12ms
< 30ms
< 5s
No answer
Communication operation and setting
Inverter response time
(Refer to the following table for the
data check time)
Response Message
Data absence time
(3.5 bytes or more)
No Response
4
229

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents