Operation Panel
rE1
Indication
Name
Parameter read error
Description
An error occurred in the EEPROM on the operation panel side during parameter copy reading.
Check point
 Make parameter copy again. (Refer to page 321.)
Corrective action
 Check for an operation panel (FR-DU07) failure. Please contact your sales representative.
Operation Panel
rE2
Indication
Name
Parameter write error
 You attempted to perform parameter copy write during operation.
Description
 An error occurred in the EEPROM on the operation panel side during parameter copy writing.
Check point
Is the FWD or REV LED of the operation panel (FR-DU07) lit or flickering?
 After stopping operation, make parameter copy again. (Refer to page 321.)
Corrective action
 Check for an operation panel (FR-DU07) failure. Please contact your sales representative.
Operation Panel
rE3
Indication
Name
Parameter verification error
 Data on the operation panel side and inverter side are different.
Description
 An error occurred in the EEPROM on the operation panel side during parameter verification.
Check point
Check for the parameter setting of the source inverter and inverter to be verified.
 Press
Corrective action
Make parameter verification again. (Refer to page 322.)
 Check for an operation panel (FR-DU07) failure. Please contact your sales representative.
Operation Panel
rE4
Indication
Name
Model error
 A different model was used for parameter write and verification during parameter copy.
Description
 When parameter copy write is stopped after parameter copy read is stopped
 Check that the verified inverter is the same model.
 Check that the power is not turned OFF or an operation panel is not disconnected, etc. during
Check point
parameter copy read.
 Use the same model (FR-F700 series) for parameter copy and verification.
Corrective action
 Perform parameter copy read again.
Operation Panel
Err.
Indication
 The RES signal is ON
 PU and inverter cannot make normal communication (contact fault of the connector)
Description
 When the voltage drops in the inverter's input side.
 When the control circuit power (R1/L11, S1/L21) and the main circuit power(R/L1, S/L2, T/L3) are
connected to a separate power, it may appear at turning ON of the main circuit. It is not a fault.
 Turn OFF the RES signal.
 Check the connection of PU and inverter.
Corrective action
 Check the voltage on the inverter's input side.
to continue verification.
Causes and corrective actions
-- ------ ------