Check the correct ventilation of the equipment:
Check the state of the ventilator filters; Proceed to clean and replace it if necessary.
Extract the filter removing previously the ventilation grid.
Beat softly the filter to separete particles fixed on the filter.
Use vacuum cleaner or similar.
If the filter continues dirty, clean it in water at 40ºC.
If the filter is oily or greasy, replace with a new one.
Check the state of the air extraction ventilator; Proceed to clean and replace it
if necessary.
Clean radiator´s fins.
Clean ventilation grids.
The inverters make a slight buzzing noise.
Check surrorroundings properties in order to avoid amplifying the buzzing.
Install the inverters in an easily accesible place so there is enough room for carrying
out installation and maintenance procedures and it is easy to use the keyboard,
read the Display and open the inverter.
Pg. 24 de 40
Installation Manual
Ingecon® Sun Three-Phase Inverter
Ref.: AAS2000IKI02
Rev.:_
Dec-2009