5. INSTALLATION.

Read and respect the Safety Information, described
in Chapter 2 of this document. Failure to obey some
of the instructions described in this manual can result in a
serious or very serious accident to persons in direct contact
or in the vicinity, as well as faults in the device and/or loads
connected to it.
In addition to the device's own user manual, other documents
are supplied on the CD-ROM or documentation pen drive.
Consult them and strictly follow the indicated procedure.
Unless otherwise indicated, all actions, instructions,
guidelines and notes are applicable to the devices, whether
or not they form part of a parallel system.
5.1. RECEPTION OF THE DEVICE.
Pay attention to section 1.2.1. of the safety instructions
-EK266*08- in all matters relating to the handling,
movement and siting of the unit.
Use the most suitable means to move the UPS while it is
packed, with a pallet jack or forklift.
Any handling of the device must be carried out in accordance
with the weights shown in the technical specifications
according to the model, indicated in Chapter 9. Annexes.
5.1.1. Reception and contents.
Reception. Check that:
The data on the label affixed to the packaging
ˆ
corresponds to that specified on the order. Once the
UPS is unpacked, check the previous data with those of
the device nameplate.
If there are discrepancies, report the issue as soon as
possible, citing the device's manufacturing number and
delivery note references.
It has not suffered any mishaps during transportation
ˆ
(packaging and impact indicator in perfect condition).
Otherwise, follow the protocol indicated on the label
attached to the impact indicator, located on the
packaging.
Unpacking.
To check the contents, it will be necessary to remove
ˆ
the packaging.
Complete the unpacking according to the
procedure of section 5.1.3.
Contents.
6 to 10kVA device:
ˆ
1 UPS.
Information for warranty registration.
The user manual in CD-ROM or pen drive format.
2 metal pieces for use as handles and screws for
installing the UPS in a rack cabinet.
1 USB cable.
4 plastic pieces for use as a base to facilitate the
arrangement of the UPS as a tower (vertical position).
1 cable for connecting the communication bus.
Useful only for connection to a parallel device.
1 cable for connecting the current bus. Useful only
for connection to a parallel device.
USER MANUAL
Battery module:
ˆ
1 battery module.
Information for warranty registration.
2 metal pieces for use as handles and screws for
installing the unit in a rack cabinet.
2 plastic extensions of 2U to extend the base of the
UPS + 1 metal piece to allow the arrangement of
the attached battery module as a tower.
1 cable for interconnecting the battery module and
another module.
Isolation transformer module:
ˆ
1 isolation transformer module.
Information for warranty registration.
2 metal pieces for use as handles for installing the
unit in a rack cabinet.
2 plastic extensions of 2U + 2 extensions of
1U + 1 metal piece to allow the arrangement of the
attached battery module as a tower.
Once the reception is completed, it is advisable to re-pack
the UPS until it is put into service in order to protect it
against mechanical shock, dust, dirt, etc.
The packaging of the device consists of a wooden pallet,
cardboard or wooden box, depending on the item, expanded
polystyrene corners, polyethylene cover and strapping, all
of which are recyclable materials. When the packaging
requires disposal, it must be carried out in accordance with
current laws.
We recommend keeping the packaging for at least 1 year.
5.1.2. Storage.
The device storage shall be done in a dry, ventilated place
and protected from rain, dust, water splashes or chemical
agents. It is advisable to keep each device, battery module
and isolation transformer in its original packaging, as it has
been specifically designed to ensure maximum protection
during transportation and storage.
For devices that contain Pb-Ca batteries, the
charging times indicated in Tab. 2 of document
EK266*08, determined by the temperature to which they
are exposed, must be respected, otherwise the warranty
may be invalidated.
After this period, connect the device to the mains together
with the battery unit if applicable, start it according to the
instructions described in this manual and charge for 12 hours.
In parallel systems, it is not necessary to interconnect de-
vices before battery charging. Each of them can be treated
independently to charge them.
Then shut down the device, disconnect it and store the UPS
and batteries in their original packaging, noting the new
date for recharging the batteries on a document as a record
or even on the packaging itself.
Do not store the devices where the ambient temperature
exceeds 50°C or drops below -15°C, as this may cause
degradation of the electrical characteristics of the batteries.