5. INSTALLATION INSTRUCTION

5.1. LOCATION
As each site has its requirements, the installation instructions
in this section are to act as a guide for the general procedures
and practices that should be observed by the installing engi-
neer.
5.1.1. Installation Environment
The UPS is intended for indoor installation and uses forced
convection cooling by internal fans. Please make sure there is
enough space for the UPS ventilation and cooling.
Keep the UPS far away from water, heat and inflammable and
explosive, corrosive material. Avoid installing the UPS in the
environment with direct sunlight, dust, volatile gases, corrosive
material and high salinity.
Avoid installing the UPS in the environment with conductive
dirt.
The operating environment temperature for battery is 20ºC-
25ºC. Operating above 25ºC will reduce the battery life, and
operation below 20ºC will reduce the battery capacity.
The battery will generate a little amount of hydrogen and
oxygen at the end of charging; ensure the fresh air volume of
the battery installation environment must meet EN50272-2001
requirements.
Module
Dimensions WxDxH
Weight
Module
Dimensions WxDxH
Weight
MANUAL DE USUARIO
Units
mm
Kg
Table 2. Module mechanical characteristics.
Units
30/10,45/15,60/20
mm
900x600x1100
Kg
120
Table 3. System mechanical characteristics.
If external batteries are to be used, the battery circuit breakers
(or fuses) must be mounted as close as possible to the batte-
ries, and the connecting cables should be as short as possible.
5.1.2. Site Selection
Ensure the ground or installation platform can bear the weight
of the UPS cabinet ,batteries and battery rack.
No vibration and less than 5 degree inclination horizontally.
The equipment should be stored in a room so as to protect it
against excessive humidity and heat sources.
The battery needs to be stored in dry and cool place with good
ventilation. The most suitable storage temperature is 20 ºC to
25ºC.
5.1.3. Size and Weight
The size of three views for the UPS cabinet is shown in Fig. 11.
Attention:
Ensure there is at least 0.8m before the front of the cabinet so
as to easily maintain the power module with the front door fully
open and at least 0.5m behind for ventilation and cooling.
10
15
590 x 440 x 134
21
22.5
60/10,90/15,120/20
900x600x1600
151
ADAPT SISTEMA DE ALIMENTACIÓN ININTERRUMPIDA
20
22.5
100/10,150/15, 200/20
900x600x2000
182
11