Siemens SIMATIC ET 200SP F-TM Equipment Manual page 24

Hide thumbs Also See for SIMATIC ET 200SP F-TM:
Table of Contents

Advertisement

Cable lengths and cable types
If you do not use an "all-in-one" plug-in cable, the following cable lengths and cable types
are permitted for the interfaces:
Table 4- 1
Wiring rules for the interfaces
Connector
Function
ENC+/ENC-
Incremental encoder
signals and supply
U/V/W
Motor phases
DI, M
Input
Ground
L+/M
Power supply, power
unit
B+
Connection of external
braking resistor
a, b, z
Encoder connectors
STO
Safe Torque Off
* American Wire Gauge
Note that connected mains lines must be designed according to the expected minimum and maxi-
mum ambient temperature.
F-TM ServoDrive
Equipment Manual, 02/2020, A5E47579503-AA
Maximum cable
Cable type
length
10 m
Shielded
For differential wiring,
one twisted pair per
signal pair
10 m
Shielded
10 m
≥ 2 m shielded
10 m
-
10 m
-
2 m
≥ 0.5 m shielded
10 m
Shielded
10 m
-
4.2 Block diagram
Cable cross-section
Solid and stranded supply cable:
AWG*: 22 to 16 or
0.34 mm
to 1.5 mm
2
2
Solid and stranded supply cable:
AWG*: 20 to 14 or
0.5 mm
to 2.5 mm
2
2
Solid and stranded supply cable:
AWG*: 22 to 16 or
0.34 mm
to 1.5 mm
2
2
For through-wiring for maximum
permissible terminal currents, use
AWG* 16 or 1.5 mm
.
2
Solid and stranded supply cable:
AWG*: 20 to 14 or
0.5 mm
to 2.5 mm
2
2
Solid and stranded supply cable:
AWG*: 18 to 16 or
1.0 mm
to 1.5 mm
2
2
Solid and stranded supply cable:
AWG*: 18 to 14 or
1.0 mm
to 2.5 mm
2
2
Solid and stranded supply cable:
AWG*: 20 to 16 or
0.5 mm
to 1.5 mm
2
2
For through-wiring for maximum
permissible terminal currents, use
AWG* 16 or 1.5 mm
.
2
Wiring
23

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents