"OPER" Slave in Operational condition (running);
"MISS" Slave 'lost;
"* "
Error condition (in or with preceding)
ID: Unique device identifier (as inserted in HW
configurator). Useful for pointing at device in PLC
code.
device name: device name (as inserted in HW
configurator).
Note on ID
Each device has a unique number (ID) for identification
(including by PLC). This number is assigned automatically,
but can be changed manually in the HW configurator.
Device section
Click on one of the listed devices to access the diagnostics
for that device.
The first line is the same as on the main menu
followed by:
Name device: device name (shown in yellow);
Diagnostic: diagnostics of slave in binary; the lower
section explains the meaning of each bit;
Status: Operating status
"----" Slave not previously communicated with;
"Init" Slave in init condition;
"Pre Operational" Slave in Pre Operational
condition;
"Bootstrap" Slave in bootstrap condition;
"Safe Operational" Slave in Safe Operational
condition;
"Operational" Slave in Operational condition
(running);
"Missing" Slave 'lost';
"(Err)" Error condition (in or with preceding);
Request Status to slave: interface to request new status
to slave: No request, Init, Pre Operational, Bootstrap,
Safe Operational, Operational;
Slave information: generic information on slave:
Vendor Id;
Product Code
Revision Number
Serial Number
Slave Error Code: slave error code;
Clear Error State: button to clear slave error state;
The lower section has two buttons:
Return to list: return to slaves list;
32
Advanced: go to diagnostics of master
Advanced section
Click on the Advanced button to access diagnostics of the
master.
The first line is the same as on the main menu
followed by:
Diagnostic: diagnostics of master in binary
The lower section explains the meaning of each bit;
Status: Operating status:
"Init" Master in init condition;
"Pre Operational" Master in Pre Operational
condition;
"Bootstrap" Master in bootstrap condition;
"Safe Operational" Master in Safe Operational
condition;
"Operational" Master in Operational condition
(running);
Request state to master: interface to request new status
to master: No request, Init, Pre Operational, Bootstrap,
Safe Operational, Operational;
The lower section has one button:
Base: to return to base interface: list of slaves or
diagnostics of slave.

GDNet

Click the GDNet button on the bottom tool bar to access
diagnostics of the network and of GDNet devices
The window shows:
a top bar describing network status,
a list of GDNet devices in the network;
the Advanced button to access advanced information.