Warning: The RS485 port is equipped with
internal termination and polarization, as shown in
the figure below.
Figura 20 - Polarizations and line termination RS485
The RS485 line polarizations and termination are settable
with jumper J2 as shown below.
See figure 15 to locate the jumper.
Figure 21 - RS485 Configuration, Polarizations and Termi-
nation
1000 m
100 m
10 m
10 kb/s
100 kb/s
Max data transmission speed with AWG24 cable
Figure 22 - RS485 max transmission speed
80949_MAN_eView BOX_05-2019_ENG
1 Mb/s
10 Mb/s

CAN

The CAN port is optional. Connect the cable for the CAN
field bus. The CAN bus is used to connect to the controller
devices that conform to the CANopen standard.
Considering that the CAN port is opto-isolated, it is not
necessary to disconnect the power to the device before
connecting it.
For the wiring of the line, use an approved cable.
Fasten the cable connector to that of the controller with the
appropriate screws.
Do not connect any filters other than the ones
described.
1
Pin
Name
1
2
CAN_L
3
GND
4
5
EARTH
6
7
CAN_H
8
9
Warning: The CAN port has a line termination. If
the CPU module is the last or the first device on
the CAN line, you have to insert the termination
(120 Ω resistance, ¼ W, 5%) by setting jumper
J1 as shown in figure 23.
Remember that the CAN bus must be
terminated at both ends.
Figure 23 - CAN bus line termination
The CAN line termination is settable with jumper J1 as shown
9
Description
CAN-Low (CAN-)
Ground (mass)
Earth
CAN-High (CAN+)
21