MOUNTING
Hole dimensions
Fig. 1
For correct installation, comply with the dimensions
of the drilling templates shown in Fig.1 and the
dimensions of the space requirements in Fig.12.
Installation note
The plate on which the Inside Control Panel
Controller is mounted must:
• be sufficiently stiff and strong to support the
Fig. 2
device and not bend during use;
• have a minimum thickness of 2 mm to allow the
holes to be threaded properly;
• have an M5 threading.
Protection against infiltrations of water
The Inside Control Panel Controller offers a degree
of protection of IP20.
When it is necessary to use the product in
environments that require a protection rating greater
than IP20, that rating must be guaranteed by the
control panel where the controller is installed.
Vibration
The Inside Control Panel Controller can support
vibrations up to 150 Hz:
• from 5 to 9 Hz: sinusoidal 3.5 mm constant;
• from 9 to 150 Hz: sinusoidal with acceleration
equal to 1 G.
Should the device be mounted on a support that
exceeds these limits it is necessary to envisage
a system for the suspension and mitigation of the
vibration.
Minimum spaces for ventilation
The temperature of the compartment that
houses the Control Panel must not exceed,
55 °C.
Fig. 3
Figure 2- Free spaces for ventilation shows the
minimum free distances recommended in the
installation of the device in a closed compartment.
Positioning
The
Inside Control Panel Controller must be
positioned to guarantee the following conditions:
• there must be no sudden temperature changes;
• there must be a low explosion risk: it can
be connected to elements that operate in
environments with a hazardous atmosphere
(flammable or explosive) only through appropriate
Fig. 4
and suitable types of interface, compliant to the
safety standards in force;
• low presence of magnetic fields.
Fastening
The Inside Control Panel Controller can be installed
in two ways:
horizontal on DIN 35 mm track, Fig.4A.
vertical, Fig.4B.
Horizontal mounting:
Install the 2 brackets for the DIN 35 track as shown
in Fig.3. Fasten the product and press hard to
complete the operation, rotating downwards.
Vertical mounting:
Prepare the M5 threaded holes, done with the
template as shown in Fig.1, position the product
and screw in place as shown in Fig.4. Warning:
install locking washers to prevent the screws from
loosening!
TECHNICAL DATA
Operating voltage
217
Current draw (at 24 VDC)
Power dissipation
POWER SUPPLY
Protections
Connection
Ethernet port (ETH)
KEY & LED port
RS-232 port (optional)
RS-485 port (optional)
CONNECTIONS
CAN port (optional)
USB port
Ethernet
COMMUNICATION
PROTOCOLS
CAN
Modbus
CONFIGURATION
Access to software procedures 16-position rotary switch
ELEMENTS
CONTROL
Touch screen
ELEMENTS
Diagnostics
VIEWING ELEMENTS
Type and frequency
MICROPROCESSOR
System
Mass
MEMORY
Mass extension
Operating temperature
Storage temperature
AMBIENT
Relative humidity
CONDITIONS
Vibrations
ASSEMBLY
PROTECTION LEVEL
WEIGHT
EMC conformity
(Electromagnetic compatibility)
EC REGULATIONS
* SD card not supplied. Available as accessory
eView BOX
24 VDC ±25%
500 mA max
12 W max
Polarity inversion
Short circuit
3-pin polarized removable connector
Screw terminals, max cable section 2.5 mm
2
Number of channels: 2 max (1 optional)
Connector: RJ45
Velocity: 10 / 100 / 1000 Mbit/s
Signals: green connection LED, yellow data LED
Connector: RJ45
Standard: USB2.0
Connector:: DB9 M
Speed: 1.2kbit/s...115kbit/s
QUICK INSTALLATION GUIDE
Optically isolated
Connector: DB9 M
Side 1
Speed: 9 kbit/s ... 19 kbit/s
Terminations and polarization: internal, selectable with
jumper
Optically isolated
Connector: DB9 M
Side 2
Speed: 20, 50, 100, 125, 250, 500, 1000 kbit/s, default
500 kbit/s
Termination: internal, selectable with jumper
Number of ports: 2 max
Connector: type A
Standard: USB 2.0
Protection: overload
FTP (File Transfer Protocol) Modbus TCP/IP Master/
Slave
Ethercat Master
WARNING and SAFETY
GDNET Master
CANopen Master
Modbus RTU Master/Slave
Gefran S.p.A. also reserves the right to make changes to the contents and form of this manual and to the charac-
teristics of the devices illustrated at any time and without prior warning.
4-wire resistive technology
The installation of the devices illustrated in the manual must be carried out by qualified technicians in compliance with
PW LED (yellow): power supply on
the laws and standards in force and in agreement with the instructions contained in the manual.
RN LED (green): PLC program state
If the eView BOX is used in applications with the risk of damages to persons, machinery or materials, its use in con-
LED E1 (red): HW Watchdog state
junction with alarms is essential.
LED E2 (red): PLC program error
It is advisable to envisage the possibility of checking the intervention of the alarms during regular operation.
ATOM E620, 0.6 GHz
Before interacting with the Inside Control Panel Controller, the operator must receive full training in the procedures of
ATOM E660, 1.3 GHz
operation, emergency, diagnostics and maintenance of the system.
512 MB, DRAM type DDR II
More information on the device and its installation, maintenance and use procedures can be found in the product's
2 GB Flash memory
Installation and User Manual, available for download on the website www.gefran.com.
SD Card Slot *
0 ... +55 °C (as per IEC 68-2-14)
-20 ... +70 °C (as per IEC 68-2-14)
max 95% RH non condensing (as per IEC 68-2-3)
The symbol showing a crossed-out wheeled bin on equipment or its packaging indicates that the product must be
5 to 9 Hz: sine constant 3.5 mm
collected separately from other waste at the end of its useful life.
10 to 150 Hz: sine acceleration 1G
The manufacturer is responsible for organising and managing the separate collection of this piece of equipment
Mounting inside the control panel, horizontally with the
at the end of its useful life.
DIN bar or vertically with fixing screws.
Users wishing to dispose of the equipment must therefore contact the manufacturer to obtain instructions from the
IP 20 (as per IEC 68-2-3)
same on how to have the equipment collected separately at the end of its useful life.
1.250 kg
By collecting the disused equipment separately, it can be recycled, treated or disposed of in an environmentally
Compliance with the 2014/30/EU Directive
friendly manner, thus helping to prevent the environment and public health from being affected negatively and
EN61131-2: Programmable controllers
enabling reuse and/or recycling of the materials forming the same equipment.
Part 2: Equipment requirements
Graphic simbol
Inside Control Panel Controller
code 81673 - 04/2019 - ENG
Warnings and safety
Technical data
Mounting
Connections
Dimensions
GEFRAN spa
via Sebina, 74 - 25050 Provaglio d'Iseo (BS)
Tel. 03098881 - fax 0309839063- Internet: http://www.gefran.com
While all the information contained in this manual has been carefully checked, Gefran S.p.A. accepts
no responsibility for the possible presence of errors or for damage to persons and/or property caused
by the improper use of the manual.
WEEE Information
Pursuant to Article 26 of Italian Legislative Decree no. 49 of 14 March 2014 "Implementation of
Directive 2012/19/EU on waste electrical and electronic equipment (WEEE)".
NOTES ON ELECTROMAGNETIC COMPATIBILITY:
CE: Conformity EMC (electromagnetic compatibility) in compliance with Directive
EN61131-2: Programmable controllers
Part 2: Equipment requirements and test.
Indicates contents of sections, general instructions, notes, and other points to which the reader's attention needs to be
called.
Indicates a particularly delicate situation that could affect the safety or correct operation of the controller, or an instruction
that MUST be followed to prevent hazards.
eView BOX
LV
2014/30/EU.

Advertisement

loading

Summary of Contents for gefran eView BOX

  • Page 1 • there must be no sudden temperature changes; VIEWING ELEMENTS If the eView BOX is used in applications with the risk of damages to persons, machinery or materials, its use in con- LED E1 (red): HW Watchdog state • there must be a low explosion risk: it can junction with alarms is essential.