Carrier RG2059 Series Operation And Service page 59

Generator set units
Table of Contents

Advertisement

Table 5–1 Preventative Maintenance Actions and Schedule (Continued)
Procedure
22.Check water pump bearing end play.
23.Change fuel filter.
24.Check crankcase breather.
25.Remove and check engine/generator shock mounts for
cracks, cuts, abrasion or flaring.
26.Clean and flush coolant system.
27.Check starter condition.
28.Check engine compression.
29.Check and adjust injector nozzles.
30.Perform generator maintenance.
31.Check total time meter operation (allow engine to run 10
minutes).
32.Listen for abnormal noises.
33.Check fuel, lubricating oil and radiator coolant lines, con-
nections and filters for leaks.
34.Check exhaust system for leaks.
35.Check with voltmeter. Generator output should be 490volts,
+ 15volts (engine, 1800 rpm) with a nominal frequency of
60Hz.
36.Turn refrigeration unit on and check generator 1800 rpm
under full load.
37.Verify operation of safety devices.
Units have mineral oil installed from the factory. Change lubricating oil and filters after the first
2000 hours of service or at the end of the first year, whichever comes first.
Oil changes after the first 2000 hour service, or 1 year:
-
If using mineral oil, oil changes should continue every 2000 hours of service or every 1 year, whichever
comes first.
-
If using specified synthetic lubricating oil and OEM extended life oil filter, oil changes should be completed
every 4000 hours of service, or every two years, whichever comes first.
1
Pre-trip maintenance checks should be carried out prior to any use of the unit (1-15 and 31-36).
2
2000 hour maintenance checks should be carried out annually or every 2000 hours, whichever comes first.
3
4000 hour maintenance checks should be carried out every two years or every 4000 hours, whichever comes first
Manual
Reference
Pre-Trip
Engine
Manual
Section
5.5.3
Section
5.5.12
Section
5.7.2
Section
5.5.5
Engine
Manual
Engine
Manual
Engine
Manual
Section 5.6
-
-
-
-
Section 5.6
Section 5.6
Section 2.9
5–19
Every
During
2000
1
hours of
hours of
2
service
service
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
Every
4000
3
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
T-361