Carrier RG2059 Series Operation And Service page 25

Generator set units
Table of Contents

Advertisement

Cooling System:
Lubrication System:
Electrical:
Table 2–6 Engine Data (Continued)
Capacity
Anti-Freeze: Extended Life
Water Temperature Safety Switch Setting:
Opens
Resets
Thermostat:
Starts to open
Fully open
Oil Pressure
Generator
6 U.S. quarts (5.68 liters) - includes 1 quart (0.95 li-
ter) in coolant recovery bottle. (Refer to
5.5.5)
The cooling system is factory charged with a 50/50
mix of extended life coolant (ELC) and deionized
water. This mixture provides protection to -34°F (-
37°C). For replacement, with extended life coolant
(ELC) meeting ASTM D4656 specification and de-
ionized water. A 50/50 mix is recommended. Ex-
tended life coolant is red or orange in color. DO NOT
mix with conventional coolant.
230 + 5°F (110 + 3°C)
200°F (93°C) - minimum
177 to 182°F (80 to 84°C)
203°F (95°C)
35 to 60 psig (3.3 to 5.2 kg/cm)
400-500 VAC @ 60 hz
360-460 VAC @ 50 hz
2–13
Section
T-361

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rg2100 series69rg15

Table of Contents